District Heating and Cooling Networks

How district heating and cooling networks work, why supply temperatures are falling, how losses scale, and which heat sources suit low-temperature networks.

Published
Reading time
8 min
Byline
Cascade
Pre-insulated district heating pipes laid in an open trench on a city street
Image: FRAWA, Pixabay Content License

A district heating network is, at heart, a very large central heating system: a heat source, a loop of insulated pipes, and many buildings drawing heat through substations instead of burning fuel in their own boilers. District cooling does the same with chilled water. The concept is more than a century old, yet it is attracting fresh interest because it can do something individual buildings cannot easily do: collect heat that would otherwise be wasted and move it to where it is needed.

Penetration varies enormously. The European Environment Agency estimates that district heating supplies about a tenth of the EU's heat, concentrated in northern, central and eastern Europe. In Denmark, district heating covers around two-thirds of building heat demand, while in several western European countries it is marginal.

This article explains how networks are designed, why the industry is moving to lower temperatures, how to estimate heat losses, and where district cooling fits.

Anatomy of a network

Every system has four parts:

  1. Heat sources — boilers, combined heat and power (CHP) plants, large heat pumps, waste-to-energy plants, industrial waste heat, geothermal wells or solar thermal fields. Most networks combine several, dispatched by cost and availability.
  2. Distribution pipes — usually pre-insulated steel or plastic pipes buried in pairs (supply and return), sometimes as twin pipes in a single casing.
  3. Substations — heat exchangers at each building that separate the network water from the building's own heating and hot-water circuits. Direct connections exist but are less common in new systems.
  4. Thermal storage and controls — hot-water tanks or pits that decouple production from demand, plus control systems that manage temperatures, pressures and plant dispatch.

The heat delivered by water flowing through a pipe follows the familiar relationship:

Q = ṁ · cp · (Tsupply − Treturn)

where ṁ is mass flow (kg/s) and cp is about 4.19 kJ/(kg·K) for water. The temperature difference between supply and return is therefore as important as the supply temperature itself. A network that returns water too warm must pump more water to deliver the same heat, which raises pumping energy and limits capacity.

Four generations, and a fifth under debate

The influential 2014 paper by Lund and colleagues framed the history of district heating as a sequence of generations, each running at lower temperature than the last.

GenerationApproximate eraHeat carrier and supply temperatureCharacteristic features
1stLate 19th century onwardsSteamHigh losses, condensate return problems, safety risks
2ndFrom the 1930sPressurised hot water, above 100 °CCoal-fired CHP, concrete ducts, site-built pipes
3rdFrom the 1970s–80sPressurised hot water, roughly 80–100 °CPrefabricated pre-insulated pipes, compact substations
4th2020s onwardsLow-temperature water, roughly 50–60 °CRenewable and waste heat, smart controls, efficient buildings

Some engineers add a "fifth generation": networks operating near ground temperature (often 10–25 °C) with heat pumps in each building, able to share heat and cooling between users. Whether this is a new generation or a different category is debated, but the concept is well suited to mixed-use districts where some buildings reject heat while others need it.

Why lower temperatures matter

Fourth-generation district heating (4GDH) aims for supply temperatures low enough to unlock heat sources that cannot reach 80–100 °C. Three benefits follow.

Lower heat losses. Losses through pipe insulation scale roughly with the difference between the mean water temperature and the surrounding ground.

Better heat pump performance. A heat pump's coefficient of performance falls as the temperature lift rises. The ideal (Carnot) limit illustrates the trend:

COPCarnot = Thot / (Thot − Tcold) (temperatures in kelvin)

Drawing heat from a 10 °C source, the Carnot COP is about 5.0 for 80 °C supply but about 7.3 for 55 °C supply. Real machines achieve perhaps half of Carnot, so the practical difference is roughly 2.5 versus 3.6: a large saving in electricity per unit of heat. Our article on heat pumps and their real-world COP explains these limits in more detail.

More usable waste heat. Data centres, supermarkets, sewage, metro tunnels and many industrial processes reject heat at 25–50 °C. At low network temperatures, this heat can be used directly or upgraded with a modest heat pump lift. Data centres are an increasingly important example as liquid cooling raises the temperature of the heat they reject.

The catch is on the demand side. Older buildings with small radiators may not be comfortable on 55 °C supply in cold weather. Successful transitions combine network changes with building measures: improved insulation, larger or additional emitters, and correcting the substation faults that raise return temperatures.

Worked example: heat losses at two temperature levels

Consider an illustrative network delivering 50 GWh of heat per year through 40 km of trench, giving a linear heat density of 50,000 MWh ÷ 40,000 m = 1.25 MWh per metre per year. Assume a combined heat-loss coefficient for the supply and return pair of 0.25 W per metre of trench per kelvin, and a ground temperature of 10 °C.

Third-generation operation (supply 80 °C, return 45 °C):

  • Mean water temperature = 62.5 °C; difference to ground = 52.5 K
  • Loss per metre = 0.25 × 52.5 ≈ 13.1 W/m, or 13.1 × 8,760 h ≈ 115 kWh/m per year
  • Total loss = 115 kWh/m × 40,000 m ≈ 4.6 GWh/year
  • Loss fraction = 4.6 ÷ (50 + 4.6) ≈ 8.4% of heat produced

Fourth-generation operation (supply 55 °C, return 25 °C):

  • Mean water temperature = 40 °C; difference to ground = 30 K
  • Loss per metre = 0.25 × 30 = 7.5 W/m, or about 66 kWh/m per year
  • Total loss ≈ 2.6 GWh/year, or about 5.0% of heat produced

The reduction in losses is useful, but notice that linear heat density drives the result as much as temperature. Halve the heat sold along the same pipes, for instance after deep building renovation, and the loss fraction roughly doubles. This is why heat density screening is the first step in any feasibility study.

Rule of thumb: networks become difficult to justify where linear heat density is low, such as suburbs of detached houses. Dense urban districts, campuses and mixed-use developments with large anchor loads are the natural territory for heat networks.

Heat sources for a low-carbon network

The heat source mix determines a network's carbon performance. A network fed by gas boilers is no greener than the buildings' own boilers, apart from scale efficiencies. Low-carbon options include:

  • Large heat pumps using sewage, river, sea, lake or ground water, or industrial waste heat as the source. They link heat networks to the electricity system and can run hardest when electricity is cheap and abundant.
  • Waste-to-energy and industrial waste heat, which use energy that would otherwise be lost. Long-term supply contracts are essential because the industrial host may change its processes or close.
  • Geothermal heat, where geology allows, either directly or with heat pump assistance.
  • Large-scale solar thermal, usually combined with seasonal storage in pits or tanks. Our article on solar thermal systems covers the collector technology.
  • CHP as a transitional or flexibility source, provided fuel and operating patterns are compatible with decarbonisation goals.

Thermal storage is the glue. A large insulated tank stores heat far more cheaply per kilowatt-hour than batteries store electricity, which lets operators shift heat pump operation to times of low electricity prices. The comparison is explored in our piece on energy storage for buildings.

District cooling

District cooling distributes chilled water, typically supplied at around 4–7 °C, from central plants to buildings. It makes most sense where cooling demand is dense and sustained: business districts, hospitals, airports and campuses in warm climates.

Central plants gain efficiency from scale, better maintenance and diversity of demand: not every building peaks at the same moment, so installed capacity can be lower than the sum of individual chillers. Additional gains come from:

  • Free cooling from cold sea, lake or river water. Toronto's deep lake water cooling system, which draws cold water from Lake Ontario, is a frequently cited example of this approach.
  • Absorption chillers driven by waste heat, useful where surplus heat is available in summer.
  • Thermal energy storage using chilled water or ice to shift chiller operation to off-peak hours.
  • Combined heating and cooling, where heat pumps produce chilled water and useful heat at the same time.

The main technical challenge is the small temperature difference. With supply at 6 °C and return at 14 °C, each kilogram of water carries only about a quarter of the energy it would in a heating network with a 35 K difference, so pipes are large and pumping energy significant. Keeping return temperatures high is to cooling networks what keeping them low is to heating networks.

Regulation, business models and consumer protection

Heat networks are natural monopolies at the level of an individual building: once connected, a customer cannot easily switch supplier. Governments have responded in different ways, from municipal ownership in Scandinavia to price regulation and consumer-protection schemes elsewhere. The EU's recast Energy Efficiency Directive defines "efficient district heating and cooling" with requirements that tighten over time towards renewable energy, waste heat and high-efficiency cogeneration, and requires heating and cooling planning in larger municipalities.

For project developers, the economics turn on four factors: heat density, anchor customers willing to sign long contracts, access to low-cost heat sources, and the cost of street works. Coordinating trenching with other utility works, as discussed in our overview of sustainable urban infrastructure, can reduce civil costs substantially.

Design priorities for the next decade

For engineers working on new or existing networks, the priorities are fairly clear:

  • Fix return temperatures first. Faulty substations, bypasses and poorly balanced building circuits are the cheapest source of improvement in most existing networks.
  • Lower supply temperatures progressively, in step with building upgrades, and use temperature-tolerant designs for new connections.
  • Plan the heat source transition from fossil boilers and CHP to heat pumps, waste heat and renewables, with storage to provide flexibility.
  • Meter and monitor at substation level, so faults are found in days rather than seasons.
  • Screen for density before extending pipes; not every street is suited to a network.

District energy is not a universal answer, but in dense urban areas it is one of the few ways to put low-grade heat from sewers, servers and factories to work.

References

  1. 4th Generation District Heating (4GDH): Integrating smart thermal grids into future sustainable energy systems (Energy, vol. 68, 2014). Elsevier / Lund et al.