Heating, Cooling and Ventilating Airport Terminals

Why terminal HVAC dominates airport energy use and how zoning, stratified air, demand-controlled ventilation, flight-linked controls and fault detection cut it.

Published
Reading time
7 min
Byline
Cascade
Airport gate lounge with tall glazing, rows of seats and air diffusers visible in the ceiling
Image: eak_kkk, Pixabay Content License

Walk through a large airport terminal and you pass through several distinct climates in a few minutes: a draughty kerbside entrance, a crowded check-in hall, a dense security queue, a sun-soaked gate lounge with floor-to-ceiling glass, a cool and cavernous baggage reclaim. Each space has its own heat gains, occupancy pattern and comfort expectations, yet they are often served by a handful of large air handling systems designed for the busiest hour of the busiest day.

That mismatch helps explain why heating, ventilation and air conditioning (HVAC) typically accounts for the largest share of terminal energy. Gu and colleagues, analysing operating data from Nanning airport in China, cite HVAC shares of roughly 41–63% of terminal energy in Chinese airports and identify passenger flow, weather and supply fan operation as leading influences. The opportunity is correspondingly large.

This article works through the terminal zone by zone, then covers the control strategies, plant choices and diagnostics that make the biggest difference.

What makes terminals thermally unusual

Four characteristics drive terminal HVAC design and energy use.

Volume. Departure halls with ceilings of 15–30 m contain enormous air volumes, but passengers occupy only the lowest two metres or so. Conditioning the whole volume uniformly wastes energy.

Glazing. Architects favour transparency for wayfinding and views of aircraft. Large glazed facades and rooflights bring daylight but also high solar gains, and cold downdraughts in winter.

Occupancy swings. Passenger numbers in a gate lounge can rise from almost zero to several hundred within half an hour of boarding, then fall to zero again. Check-in and security areas follow the flight-bank pattern of the schedule.

Openings. Kerbside doors, airside doors and baggage openings allow continuous infiltration. Tall terminals also experience stack effect, with warm air escaping at high level and cold air drawn in at ground level during winter.

Zone by zone

Kerbside entrances and check-in halls

Infiltration dominates near entrances. Vestibules with two sets of doors, revolving doors where passenger flows allow, and well-designed air curtains reduce it. Inside large check-in halls, low-level supply or displacement ventilation can condition the occupied zone while allowing warmer air to stratify above. Heat from lighting, baggage belts and equipment rises with that air and can be extracted at high level before it reaches the occupied zone.

Security screening

Security areas combine high occupant density, queues of variable length, and heat from screening equipment. They are often enclosed with lower ceilings, so they behave more like conventional rooms. Demand-controlled ventilation responds well here because occupancy is high but intermittent.

Gate lounges and piers

Piers are typically long, narrow and heavily glazed, with intense solar gains on sunny afternoons and large occupancy swings tied to individual flights. They are prime candidates for:

  • External or integrated shading and high-performance glazing to limit solar gain at source
  • Radiant floor cooling, which can absorb solar radiation falling directly on the floor before it becomes a convective load, and operates with relatively high chilled-water temperatures
  • Flight-schedule-linked control, pre-conditioning a gate area shortly before boarding and setting it back when no flights are scheduled

Baggage reclaim and back-of-house

Reclaim halls are used intermittently and passengers remain for limited periods, so comfort bands can be wider. Baggage handling areas behind the scenes are industrial spaces where the priority is worker safety and equipment protection rather than passenger comfort.

Ventilation: matching air to people

Outdoor air must be supplied for occupants, but every cubic metre must be filtered, heated or cooled, and moved by fans. Ventilation standards such as ASHRAE 62.1 and EN 16798-1 define rates that combine a component per person with a component per floor area.

At steady state, the outdoor air needed to hold indoor CO₂ at a given level above outdoor concentration follows from a simple mass balance:

Q = G / (Cin − Cout)

where G is the CO₂ generation rate per person (roughly 0.005 L/s for a seated adult, higher when walking with luggage) and the concentration difference is expressed as a volume fraction. Holding indoor CO₂ about 700 ppm above outdoor air requires roughly 0.005 ÷ 0.0007 ≈ 7 L/s per seated person. Demand-controlled ventilation (DCV) uses CO₂ sensors or people counts to vary outdoor air with actual occupancy; our article on demand-controlled ventilation covers sensor placement and control logic.

Worked example: DCV in a gate lounge

Consider an illustrative gate lounge with a design occupancy of 400 people and a design outdoor air flow of 4.0 m³/s. Over a winter operating day, average occupancy is about 35% of design, and DCV reduces the average outdoor air flow to 2.0 m³/s (it cannot fall to 35% because a floor-area component and minimum flows remain).

The sensible heating saved is:

Φ = ρ · cp · ΔV̇ · ΔT

With ρ = 1.2 kg/m³, cp = 1.006 kJ/(kg·K), a flow reduction of 2.0 m³/s and an average difference of 15 K between supply and outdoor air (after heat recovery, this difference would be smaller):

  • Φ = 1.2 × 1.006 × 2.0 × 15 ≈ 36 kW
  • Over 2,000 heating hours, that is about 72 MWh of heat per year

Fan energy falls too. The fan affinity laws state that, for a given system, power varies roughly with the cube of flow:

P2 / P1 ≈ (V̇2 / V̇1)3

Halving the flow could in theory cut fan power to one-eighth. In practice, duct static pressure setpoints, filters and minimum speeds limit the reduction, but savings of well over half are common when pressure setpoints are reset intelligently.

Plant: producing heat and cooling efficiently

Terminal central plant typically includes chillers, cooling towers or dry coolers, boilers or heat pumps, pumps and a heat recovery system. Efficiency priorities include:

  • Raising chilled-water temperatures where terminal units allow, especially with radiant systems, to improve chiller efficiency
  • Heat recovery from exhaust air and from chiller condensers to preheat outdoor air or domestic hot water
  • Free cooling in cooler seasons using dry coolers or cooling towers
  • Thermal storage to shift cooling production and reduce peak electrical demand
  • Electrification of heating through large heat pumps, increasingly replacing gas boilers as airports pursue net zero for Scope 1 emissions; see our explainer on heat pumps and real-world COP

Refrigerant choice matters as much as efficiency for the climate impact of cooling plant. Leakage of high-GWP refrigerants can offset a meaningful share of efficiency gains, which is why airports replacing chillers increasingly consider low-GWP alternatives, as discussed in refrigerants and climate.

Smoke control comes first. Terminal HVAC systems often double as smoke control systems. Any change to fan control, damper logic or zoning must be checked against the fire strategy and agreed with the fire engineer and authorities.

Controls and data: linking HVAC to operations

The most distinctive opportunity at airports is that occupancy is, to a large extent, predictable. Flight schedules, gate allocations and passenger forecasts are known hours or days in advance. Linking these operational data to the building management system allows:

  1. Gate-by-gate scheduling of ventilation and conditioning
  2. Pre-cooling or pre-heating before peaks, using building thermal mass
  3. Setback of unused piers during low-traffic periods, such as overnight or in off-peak seasons
  4. Forecast-based plant sequencing, starting chillers or heat pumps in anticipation of load rather than in reaction to it

Such integration needs careful cybersecurity and data governance, since operational systems are safety- and security-critical.

Faults: the hidden energy cost

Even well-designed systems drift. Stuck dampers, leaking valves, failed sensors, simultaneous heating and cooling, and overridden schedules are common in large air handling systems and can persist for months unnoticed in a building as complex as a terminal. Automated fault detection and diagnostics continuously checks system behaviour against rules or models and flags anomalies for engineers to investigate.

Airport terminals were the subject of early research on this approach. The European FP7 project CASCADE (October 2011 to March 2015), coordinated by Fraunhofer ISE, combined ISO 50001-based energy management with FDD for HVAC systems at pilot sites in Rome Fiumicino Terminal 1 and Milan Malpensa. Early in the pilot work, the monitoring identified control and sensor faults in air handling units at Fiumicino. The project's final results reported savings potential of up to 20%, and at Fiumicino Terminal 1 identified savings of about 363 MWh of electricity, 691 MWh of heat and 527 MWh of chilled water per year. Archived material from that historical project is available in the CASCADE archive.

A terminal HVAC improvement checklist

  • Separate metering for each major air handling unit group, chiller plant and heating plant
  • Zone-level schedules tied to flight and gate data
  • CO₂ or occupancy-based ventilation in high-variability zones
  • Static pressure and supply air temperature reset strategies
  • Stratification-friendly air distribution in tall spaces
  • Shading and glazing upgrades on the most solar-exposed facades
  • Heat recovery and free cooling maximised
  • Continuous fault detection with a clear process for acting on alerts
  • Smoke control and life safety verified after every change

Key takeaways

  • HVAC is usually the largest energy use in terminals, driven by volume, glazing, infiltration and fluctuating occupancy.
  • Conditioning the occupied zone rather than the whole volume, and controlling solar gain at source, are the foundations of efficient design.
  • Predictable occupancy from flight schedules is an unusually powerful control input.
  • Fault detection addresses the waste that accumulates in large, complex systems over time.

References

  1. Standards 62.1 and 62.2: Ventilation and Acceptable Indoor Air Quality. ASHRAE
  2. Analysis to energy consumption characteristics and influencing factors of terminal building based on airport operating data (Sustainable Energy Technologies and Assessments, vol. 44, 2021). Gu et al. / University of Reading repository
  3. The Future of Cooling. International Energy Agency
  4. CASCADE: reducing energy use by airports. CORDIS, European Commission