Fault Detection and Diagnostics in Building Systems
How fault detection and diagnostics finds hidden HVAC faults: common faults, rule-based checks such as APAR, a worked air-handler example and how to deploy FDD.

Heating, ventilation and air-conditioning systems rarely fail dramatically. Far more often they fail quietly. An outdoor-air damper sticks half open, a chilled-water valve leaks through, a temperature sensor drifts by three degrees, or someone puts a fan into manual override during a complaint and nobody puts it back. Occupants may notice nothing, because other parts of the system compensate. The energy meter notices everything.
Fault detection and diagnostics (FDD) is the practice of using data the building already produces, from the building management system and meters, to find these problems automatically. This article describes the kinds of faults that waste energy, the main families of FDD methods, a worked example of a rule-based check on an air-handling unit, the evidence on savings, and how to deploy FDD so that it leads to fixes rather than an ignored inbox of alarms.
Faults that waste energy quietly
The table summarises faults that appear again and again in commercial buildings.
| Fault | Typical symptom in data | Energy consequence |
|---|---|---|
| Outdoor-air damper stuck or mis-calibrated | Mixed-air temperature inconsistent with damper command | Excess heating or cooling of outdoor air; or poor air quality if stuck closed |
| Simultaneous heating and cooling | Heating and cooling valves both open in the same unit or zone | Energy spent fighting itself |
| Leaking (passing) valve | Coil temperature change when valve commanded closed | Unwanted heating or cooling, compensated elsewhere |
| Sensor drift or bias | Disagreement between redundant sensors; implausible values | Wrong control decisions across a whole loop |
| Schedule or override errors | Plant running outside occupied hours | Pure waste, often large |
| Economiser not working | No free cooling when outdoor conditions allow | Unnecessary mechanical cooling |
| Hunting control loops | Oscillating valve or damper positions | Wear, discomfort and inefficiency |
| Static pressure or temperature setpoints not reset | Fixed setpoints regardless of demand | Higher fan and plant energy than necessary |
Many of these faults are invisible from the operator's graphics, which show current values rather than relationships over time. FDD works by checking those relationships continuously.
Three families of methods
FDD methods are usually grouped into three broad families, which are compared in more detail in our article on fault detection research approaches.
Rule-based methods encode expert knowledge as if-then rules: "if the unit is in heating mode and the supply air is colder than the mixed air, there is a fault". They are transparent, need no training data and are easy to explain to operators. Their weakness is that thresholds must be tuned to avoid false alarms, and rules must be written for each equipment type.
Model-based methods compare measurements with predictions from a physical or grey-box model of the equipment. A coil model, for example, predicts outlet temperature for a given flow and valve position; a large residual signals a fault. They can be precise but need engineering effort to build and calibrate.
Data-driven methods learn normal behaviour from historical data, using statistical techniques or machine learning, and flag departures from it. They scale well across many buildings but need good-quality training data, may struggle to explain why something is a fault, and can learn faulty behaviour as normal if trained on a building that was never right.
In commercial practice, rule-based checks remain the backbone of most FDD products, often supplemented by data-driven anomaly detection.
Rules in practice: the APAR example
One of the best-known rule sets is APAR (air-handling unit performance assessment rules), developed at the US National Institute of Standards and Technology. APAR first determines the unit's operating mode from control signals (heating, economiser cooling, mechanical cooling with or without economiser), then evaluates only the rules relevant to that mode. It was designed to be simple enough to embed in commercial controllers, using sensor data and control signals already available. Field testing found it could detect problems such as an outdoor-air damper stuck open and manual overrides of the mixing-box damper signal.
Typical APAR-style checks include:
- in heating mode, the supply-air temperature should exceed the mixed-air temperature (allowing for fan heat);
- the mixed-air temperature should lie between the return-air and outdoor-air temperatures;
- when the cooling valve is fully closed, supply air should not be significantly colder than mixed air;
- the heating and cooling valves should not both be open at once.
Worked example: excess outdoor air
The outdoor-air fraction of an air-handling unit can be estimated from three temperatures:
OAF = (Tmix − Tret) ÷ (Tout − Tret)
Suppose, on a winter morning, the return air is 22 °C, outdoor air 2 °C and mixed air 16 °C.
OAF = (16 − 22) ÷ (2 − 22) = −6 ÷ −20 = 0.30
The control sequence calls for minimum outdoor air of 15% during occupied heating, so the unit is admitting roughly twice the intended fresh air. If supply airflow is 10 m³/s, the excess outdoor air is 0.15 × 10 = 1.5 m³/s. The extra heating required to bring it from 2 °C to 22 °C is approximately:
Q = ṁ × cp × ΔT = (1.5 × 1.2) kg/s × 1.005 kJ/(kg·K) × 20 K ≈ 36 kW
Thirty-six kilowatts of heating, for every occupied hour of the heating season, caused by a damper linkage or a mis-calibrated actuator. Nobody would see it on a graphic showing "damper 15%". An FDD rule comparing calculated and commanded outdoor-air fraction finds it on the first cold morning. (The calculation is unreliable when outdoor and return temperatures are close, so good rules only apply it when the temperature difference is large enough.)
From detection to diagnosis to action
Detection says something is wrong; diagnosis says what and where; action fixes it. Most of the value is lost between the second and third steps. Successful programmes tend to:
- Prioritise by impact. Rank faults by estimated energy cost, comfort risk and equipment risk, so the team sees the five things worth fixing this week rather than five hundred alerts.
- Suppress noise. Require a fault to persist before alerting, and tune thresholds per building.
- Route faults into maintenance workflows. Raise work orders in the computerised maintenance system rather than sending emails.
- Close the loop. Confirm that the fault clears after repair and track time to resolution.
FDD and alarms are related but distinct; our article on automated alarms for energy waste discusses how to design alerts that people act on. FDD also overlaps with condition-based maintenance, explored in predictive maintenance for building services.
The evidence on savings
The Smart Energy Analytics Campaign, coordinated by Lawrence Berkeley National Laboratory for the US Department of Energy, collected results from organisations using energy management and information systems across thousands of buildings. Its 2019 report found median whole-building savings of around 9% among organisations using FDD, after about two years. These are whole-building figures from self-selected participants, so they include other improvements, but they are consistent with the experience that FDD's main value is in finding operational faults that conventional maintenance misses.
A historical example: airports
Airport terminals are a demanding environment for FDD: very large air-handling plant, long operating hours and varying occupancy. Between October 2011 and March 2015, the EU-funded FP7 project CASCADE, coordinated by Fraunhofer ISE, developed ICT tools for energy-efficient airports that combined an ISO 50001 energy management approach with FDD for HVAC systems. Pilots ran at Rome Fiumicino Terminal 1 and Milan Malpensa. According to the CORDIS project summary, the system flagged control and sensor faults in large air-handling units supplying Fiumicino Terminal 1 after six months of piloting, alongside equipment running when not needed and poorly positioned sensors. The project's historical materials are kept in our project archive, and the wider context of terminal ventilation is covered in heating, cooling and ventilating airport terminals.
Getting started
- Check the data. FDD needs reliable trends at 15-minute intervals or better on key points: temperatures, valve and damper commands, fan status, setpoints. Fix broken sensors first.
- Tag the points. Consistent naming or a semantic model makes rules portable across equipment.
- Start with high-value rules. Schedules, simultaneous heating and cooling, economiser operation and outdoor-air fraction catch a large share of waste.
- Pilot on a few systems, tune thresholds, and confirm that findings are real before scaling.
- Integrate with maintenance so that each confirmed fault becomes a work order with an owner.
- Report outcomes, including faults fixed and estimated energy avoided, to sustain support.
FDD is most effective as part of a well-run control system, so the foundations described in intelligent building management systems are a prerequisite rather than an optional extra.
References
- An expert rule set for fault detection in air-handling units. National Institute of Standards and Technology
- Smart Energy Analytics Campaign reveals continued energy and cost savings. US Department of Energy
- CASCADE: reducing energy use by airports. CORDIS, European Commission
- ICT for Energy Efficient Airports (CASCADE), project 284920. CORDIS, European Commission