Fault Detection Research: Rule-Based, Model-Based and Data-Driven Approaches
A research guide to fault detection and diagnosis in building HVAC: rule-based, model-based and data-driven methods, how they are evaluated and open gaps.

A stuck damper, a leaking valve, a sensor reading three degrees high or a schedule that never switches the plant off at weekends: faults like these are everywhere in building HVAC systems. Individually they are mundane. Together they waste a substantial share of building energy and degrade comfort, often for years, because nothing alarms and nobody notices.
Automated fault detection and diagnosis (FDD) has been a research topic for more than three decades. The field has developed a recognisable family of methods, each with characteristic strengths and blind spots. This article surveys that landscape at a level useful to researchers, graduate students and technically minded practitioners. It covers the standard taxonomy, how each class of method works, how FDD performance is measured and the research questions that remain open. For an operational introduction, see our article on fault detection and diagnostics in building systems.
Detection, diagnosis and beyond
The literature separates several tasks:
- Fault detection: recognising that something is wrong.
- Fault isolation and diagnosis: identifying which component or fault type is responsible.
- Fault impact evaluation: estimating the consequences in energy, cost or comfort, which is needed to prioritise action.
- Prognostics: predicting degradation before a failure occurs, linking FDD to predictive maintenance.
Most published methods concentrate on detection and diagnosis. Impact evaluation and prognostics are less mature.
A standard taxonomy
Two widely cited reviews from Pacific Northwest National Laboratory provide the field's usual classification. Katipamula and Brambley's two-part review was published in HVAC&R Research in 2005, and Kim and Katipamula updated it in Science and Technology for the Built Environment in 2018. Methods fall into three broad classes:
| Class | Basis | Examples | Strengths | Weaknesses |
|---|---|---|---|---|
| Quantitative model-based | First-principles or grey-box physical models | Component models of coils, fans, chillers; residual generation | Physically interpretable; can detect subtle deviations | Model development and parameterisation effort; sensitivity to model error |
| Qualitative model-based | Rules, qualitative physics, expert knowledge | Expert rules, limit checks, qualitative models | Transparent; low data needs; easy to deploy | Thresholds need tuning; limited to anticipated faults |
| Process history-based (data-driven) | Statistical or machine-learning models trained on data | Regression, principal component analysis, classifiers, neural networks | Can capture complex behaviour; scale with data | Need representative (often labelled) data; limited transferability and interpretability |
Kim and Katipamula's review found process history-based methods to be the most common in the literature surveyed, with quantitative model-based methods the least used, mainly because of their development effort. In commercial products, rule-based approaches remain dominant because they are transparent and easy to configure.
Rule-based methods
The best-known example is the set of air-handling unit performance assessment rules (APAR) developed at the US National Institute of Standards and Technology. Rules encode expected relationships between measured variables in each operating mode. A simplified example for an air-handling unit in heating mode, with the cooling coil off:
Tsupply < Tmixed + ΔTfan − εt ⇒ fault
In words: with only the heating coil active, supply air should be at least as warm as mixed air plus the temperature rise across the supply fan. Here εt is a tolerance covering sensor uncertainty.
Illustration. Suppose mixed air is at 14 °C, fan heat adds 1 K and the tolerance is 1.5 K. Any supply temperature below 14 + 1 − 1.5 = 13.5 °C while in heating mode breaks the rule. That suggests a leaking chilled-water valve, a faulty sensor or a mode-detection error.
Rule-based methods are easy to explain to operators, need no training data and can be deployed on existing building management system (BMS) points. Their weaknesses are threshold tuning (too tight and they produce false alarms, too loose and they miss faults), rule conflicts and an inability to detect faults no one anticipated. Large rule sets are hard to maintain across varied plant.
Model-based methods
Quantitative model-based FDD compares measured behaviour with a model's prediction and analyses the residuals. A model of a cooling coil, for example, predicts outlet air temperature from inlet conditions, water flow and water temperature. A persistent residual beyond a statistical threshold indicates a fault, and the pattern of residuals across several models can help isolate it.
Model types range from detailed physical models to grey-box models, which combine physical structure with parameters identified from data. Their advantage is physical meaning. Their difficulty is the effort and data needed to configure models for each building's equipment.
Qualitative models offer a middle path. Rather than precise equations, they describe how variables should move together, for example "if the valve opens, the coil outlet temperature falls". In the FP7 project CASCADE (2011–2015), Fraunhofer ISE researchers applied qualitative-model FDD to air-handling units at Rome Fiumicino airport. In June 2014 they identified a significant cooler fault in an air-handling unit. A related paper, presented at IFAC SAFEPROCESS 2015 and published in IFAC-PapersOnLine, examined how tensor decomposition methods can reduce the size of qualitative models so that they remain computationally tractable for larger systems. An independent archive of the project's public record is available at /cms/, with its papers listed on the CASCADE publications page.
Data-driven methods
Data-driven FDD learns normal or faulty behaviour from historical data:
- Unsupervised anomaly detection models normal operation, using regression, principal component analysis, clustering or autoencoders, and flags deviations. It needs no labelled faults but cannot diagnose on its own.
- Supervised classification trains classifiers such as decision trees, support vector machines or neural networks on labelled examples of faults. It can diagnose, but labelled data from real buildings are scarce. Much research therefore relies on laboratory test rigs or simulated faults.
- Hybrid approaches combine physics with data, for example using model residuals as features for a classifier, or rule-based labelling to generate training data.
The central challenge is transferability. A model trained on one air-handling unit, building or climate often performs poorly on another. Research into transfer learning, physics-informed features and standard metadata (so that algorithms can find the right data points automatically) addresses this directly.
How FDD performance is measured
Comparing methods requires agreed metrics and data. A confusion matrix is the starting point.
Worked example (illustrative). An FDD tool evaluates 1,000 air-handling-unit days, of which 50 contain a real fault. It flags 60 days, 40 of them correctly.
| Fault present | No fault | |
|---|---|---|
| Flagged | 40 (true positives) | 20 (false positives) |
| Not flagged | 10 (false negatives) | 930 (true negatives) |
- Detection rate (recall) = 40 ÷ 50 = 80%
- False alarm rate = 20 ÷ 950 ≈ 2.1%
- Precision = 40 ÷ 60 ≈ 67%
A false alarm rate of 2% sounds low, yet one in three alerts is wrong. That is enough to erode operators' trust. Because faults are rare relative to normal operation, precision and false alarms per week often matter more to users than overall accuracy. Detection delay and diagnostic accuracy are further important measures.
Shared infrastructure: test rigs, datasets and collaboration
International collaboration has shaped the field. The International Energy Agency's Energy in Buildings and Communities programme ran Annex 25 on real-time HVAC simulation and fault detection (1991–1995) and Annex 34 on computer-aided evaluation of HVAC system performance (1997–2001). These projects produced lists of typical faults, test rigs, prototype tools and field trials that later work built on.
More recently, the field has moved towards openly published datasets of faulty and fault-free operation from laboratory and simulation studies, and towards semantic metadata schemas that let FDD software map to BMS points across buildings. Both are prerequisites for fair benchmarking and for deploying algorithms at scale through intelligent building management systems.
Open research questions
- Fault impact estimation: how much energy, cost or comfort does each detected fault cost, so that repairs can be prioritised? Reviews consistently identify this as under-researched.
- Transferability: can methods trained or tuned in one building work in another with minimal configuration?
- Benchmarking: which shared datasets and protocols allow fair comparison between rule-based, model-based and data-driven methods?
- Sensor faults: how can FDD separate faulty equipment from faulty sensors, when the method relies on those same sensors?
- Human factors: how should results be presented so that operators act on them? Who is responsible for responding?
- Large, complex facilities: how do methods scale to sites with thousands of points and heterogeneous plant, such as hospitals, campuses and airport terminals?
Choosing an approach in practice
- Start with rule-based checks on available BMS data. They are transparent and quick to deploy.
- Add model-based analysis for critical, energy-intensive equipment, such as chillers and large air-handling units, where the configuration effort pays back.
- Use data-driven anomaly detection across large portfolios to find unusual behaviour that rules do not anticipate.
- Measure precision and false alarm rates in operation, not just in testing, and tune thresholds accordingly.
- Close the loop: make sure every confirmed fault leads to a work order and a verified fix.
The methods are mature enough to deliver real value. The remaining challenges are less about inventing new algorithms than about data, integration and making sure detected faults actually get fixed.
References
- A review of fault detection and diagnostics methods for building systems (Kim and Katipamula, 2018). Science and Technology for the Built Environment
- Methods for fault detection, diagnostics and prognostics for building systems: a review, Part I. Pacific Northwest National Laboratory
- EBC Annex 25: Real Time HVAC Simulation. IEA Energy in Buildings and Communities Programme
- EBC Annex 34: Computer-Aided Evaluation of HVAC System Performance. IEA Energy in Buildings and Communities Programme
- Fault detection with qualitative models reduced by tensor decomposition methods. IFAC-PapersOnLine