Demand-Controlled Ventilation: Fresh Air Without the Waste

How demand-controlled ventilation matches fresh air to occupancy: CO₂ mass balance, worked savings, minimum rates, design pitfalls and commissioning checks.

Published
Reading time
6 min
Byline
Cascade
A large, partly occupied lecture theatre with ceiling ventilation diffusers
Image: WOKANDAPIX, Pixabay Content License

A lecture theatre designed for 200 students is ventilated, in many buildings, as though it holds 200 students from eight in the morning until six at night. In reality it may be full for two hours, a third full for three more, and empty the rest of the time. Every cubic metre of outdoor air brought in has to be filtered, moved by fans, and heated or cooled to room temperature. Supplying design airflow to an empty room is pure waste.

Demand-controlled ventilation (DCV) adjusts the outdoor airflow to match the actual need, usually inferred from CO₂ concentration or occupancy sensing. Done well, it saves energy while maintaining or improving air quality. Done badly, it can under-ventilate spaces or simply never work. This article explains the physics, works through the numbers, and sets out the design and commissioning details that decide which outcome you get.

Ventilation as an energy load

The heating or cooling power needed to condition outdoor air is:

Q = V̇ × ρ × cp × ΔT × (1 − ε)

where V̇ is the outdoor airflow (m³/s), ρ air density (about 1.2 kg/m³), cp specific heat of air (about 1.005 kJ/(kg·K)), ΔT the temperature difference between indoor and outdoor air, and ε the effectiveness of any heat recovery. In humid climates, the latent load from dehumidifying outdoor air adds substantially to the cooling requirement.

Fan energy comes on top. Fan power falls steeply with flow: for an ideal fan system, power varies with the cube of flow. Real systems with duct pressure control save less than the cube law suggests, but the reduction is still significant. In densely occupied spaces with long operating hours, ventilation can be the largest single HVAC load.

How DCV works

The control principle is simple: measure a signal that indicates how many people are present, and set outdoor airflow accordingly. Three signals are common.

  • CO₂ concentration. People exhale CO₂ at a rate that depends on body size and activity. In a space with steady occupancy and ventilation, indoor CO₂ settles at a level that reflects outdoor air per person. CO₂ is the most widely used DCV signal.
  • Occupancy sensing. Presence detectors switch ventilation between occupied and unoccupied rates; people-counting sensors at doors or overhead can estimate numbers directly.
  • Schedules and bookings. Room booking systems or timetables set airflow in advance, sometimes combined with sensors to correct for no-shows.

Many systems combine signals: occupancy sensing to drop to a minimum when the room is empty, and CO₂ to modulate between minimum and design airflow when it is occupied.

The steady-state CO₂ equation

For a well-mixed space at steady state, a mass balance links outdoor air per person to the CO₂ difference between indoors and outdoors:

V̇o = G ÷ (Cin − Cout)

where V̇o is outdoor airflow per person (L/s), G the CO₂ generation rate per person (L/s), and the concentrations are expressed as volume fractions (1 ppm = 10⁻⁶).

CO₂ generation rates vary with age, body size and activity. Persily and de Jonge, in work published by NIST, tabulate rates by these factors; for adults doing office-type work, values are in the order of 0.005 L/s per person. Using that round figure, if indoor CO₂ is 700 ppm above outdoor:

V̇o = 0.005 ÷ (700 × 10⁻⁶) ≈ 7.1 L/s per person

This relationship lets a controller translate a CO₂ setpoint into an equivalent ventilation rate per person. It also shows why outdoor CO₂ matters. NOAA reported a global average of about 423 ppm in 2024, and urban concentrations can be higher. Systems that assume a fixed outdoor value, rather than measuring it or using a realistic local figure, introduce a systematic error into their ventilation rate.

Two cautions apply. First, real rooms take time to reach steady state, especially those with high ceilings or short occupancy periods, so CO₂ lags the arrival of people. Controllers need to account for this, for example by starting ventilation at a minimum rate before occupancy. Second, the relationship assumes good mixing; in large spaces, sensor location strongly affects what the controller "sees".

CO₂ is a proxy, not the target

CO₂ at typical indoor concentrations is mainly an indicator of occupant-related pollutants and odours. It says nothing about emissions from building materials, furnishings, cleaning products or processes, which occur whether or not anyone is present.

For this reason, ventilation standards typically combine a people component and a building component. ASHRAE Standard 62.1's ventilation rate procedure, for example, calculates outdoor air from a rate per person plus a rate per unit floor area. DCV may reduce the people component as occupancy falls, but the area component remains. The design must keep a minimum outdoor airflow that addresses building-related pollutants during occupied hours, plus any pre-occupancy purge the design calls for.

Worked example: a lecture theatre

Consider an illustrative 200-seat lecture theatre with a design outdoor airflow of 2.0 m³/s (10 L/s per person). Suppose that DCV reduces average outdoor airflow by 1.0 m³/s across 2,500 hours of the heating season, with an average indoor-outdoor temperature difference of 12 K and a heat recovery unit with 75% effectiveness.

Q = 1.0 × 1.2 × 1.005 × 12 × (1 − 0.75) ≈ 3.6 kW

Annual heating saving ≈ 3.6 kW × 2,500 h ≈ 9,000 kWh

Without heat recovery, the same calculation gives about 14.5 kW and 36,000 kWh, which is why DCV has the largest benefit where heat recovery is absent or limited. Fan energy savings add to this, as do cooling savings in summer. The building energy savings calculator helps translate results like these into costs.

The numbers show that DCV is most valuable in spaces with high design occupancy, highly variable actual occupancy, long operating hours, large temperature differences and limited heat recovery: lecture theatres, auditoriums, gyms, conference rooms, and airport gate lounges. Our article on airport terminal HVAC discusses the latter.

Regulatory context

Energy codes increasingly require DCV in dense spaces. ASHRAE Standard 90.1, for example, has required DCV for spaces larger than 500 ft² (about 46 m²) with a design occupancy of at least 25 people per 1,000 ft² (roughly 27 people per 100 m²), subject to conditions on system type. In the European Union, the recast Energy Performance of Buildings Directive, (EU) 2024/1275, requires building automation and control systems in larger non-residential buildings and includes provisions on monitoring indoor environmental quality, which supports the infrastructure DCV needs. Local building regulations and national standards determine the specific ventilation rates to use.

Design and commissioning pitfalls

DCV systems fail in predictable ways.

  • Sensor location. Sensors near doors, windows or supply diffusers read low; sensors in return ducts may average across zones and hide a crowded room.
  • Calibration drift. CO₂ sensors drift, and automatic baseline correction can misbehave in spaces that never fall to outdoor levels. See our guide to smart sensors for energy management.
  • Minimum airflow settings. If terminal unit minimum airflows are set high for other reasons, such as heating or air distribution, DCV may have little room to reduce outdoor air.
  • Air-handling unit logic. Zone-level DCV must feed through to outdoor-air damper control at the air-handling unit. In multiple-zone systems this needs careful sequencing.
  • Overrides. Fans left in manual or schedules set to "always occupied" defeat the control.
  • No verification. Many DCV systems are installed but never tested under real occupancy.

Commissioning checklist

  1. Confirm each CO₂ or occupancy sensor location against the design and against actual furniture layouts.
  2. Check sensor readings against a calibrated reference at commissioning.
  3. Verify minimum outdoor airflow for building-related pollutants is maintained during occupied hours.
  4. Test the response from empty to full occupancy and back, checking damper and fan response.
  5. Confirm the air-handling unit outdoor-air damper responds to zone demand.
  6. Trend CO₂, airflow and damper position for at least several weeks after handover.
  7. Schedule periodic sensor checks and review trends seasonally.

DCV is one of the most effective strategies available to an intelligent building management system, and occupancy-based variants raise the privacy considerations covered in occupancy sensing in buildings. The principle is sound: ventilate for the people who are actually there, while never forgetting the building itself.

References

  1. ANSI/ASHRAE Standards 62.1 and 62.2: Ventilation and acceptable indoor air quality. ASHRAE
  2. Carbon dioxide generation rates from building occupants (Persily and de Jonge, 2017). National Institute of Standards and Technology
  3. Climate change: atmospheric carbon dioxide. NOAA Climate.gov
  4. Directive (EU) 2024/1275 on the energy performance of buildings (recast). EUR-Lex, Publications Office of the European Union