Building Energy Savings Calculator

Estimate kWh, cost, payback and CO2e savings from LED, HVAC scheduling, fault detection, drives, insulation and heat pumps, with measures combined correctly.

Inputs

Changes the currency symbol only. Enter tariffs in the currency you choose.
Baseline annual energy use
From 12 months of bills or meter data.
Fuel input to the boiler, not heat delivered.

How the electricity divides between end uses. The three shares must total 100%.

Tariffs and investment
Enter 0 to skip the payback.
Energy-saving measures

Tick the measures you plan. Percentages are editable planning assumptions, not guarantees. Measures on the same end use combine multiplicatively, not by adding percentages.

Emission factors (kg CO₂e per kWh)
Approximate averages; use your supplier's or country's figure.

Results

Total energy saved

–

Electricity saved (net)
–
Heating fuel saved
–
Annual cost saving
–
Simple payback
–
CO₂e avoided
–

Savings by end use

End useBaseline kWhCombined savingkWh saved

kWh saved per end use

    Estimates for screening and budgeting. Verify real savings with metered data before and after (see the explainer below).

    How the calculation works

    The calculator splits annual electricity into lighting, HVAC (fans, pumps and cooling) and other loads, and treats heating fuel separately. Each measure acts only on the end uses it affects:

    Baseline end use (kWh) = annual electricity × end-use share

    Combined saving = 1 − (1 − s₁) × (1 − s₂) × … × (1 − sₙ)

    kWh saved = baseline end use × combined saving

    Savings are combined multiplicatively because each measure saves a share of what is left after the others. A 50% LED retrofit followed by 25% from lighting controls saves 1 − 0.50 × 0.75 = 62.5% of lighting energy, not 75%: the controls are switching lamps that already use half the power. Adding percentages overstates savings and can exceed 100%.

    A heat pump is applied last. The remaining boiler fuel is replaced, and the heat pump electricity is fuel × boiler efficiency ÷ COP. Then:

    Cost saved = net electricity saved × electricity tariff + fuel saved × fuel tariff

    CO₂e saved = net electricity saved × grid factor + fuel saved × fuel factor; payback = investment ÷ annual cost saved

    Default assumptions

    • Measure percentages (LED 50%, lighting controls 25%, scheduling 10%, fault detection 8%, variable-speed drives 15%, envelope 20%) are mid-points of commonly quoted planning ranges, shown beside each input. They are not statistics for your building; replace them with audit or supplier figures.
    • Grid factors: EU-27 2024 average 0.213 kg CO₂/kWh (Ember, European Electricity Review 2025); UK 0.207 (DESNZ 2024 greenhouse gas conversion factors); USA 0.373 (US EPA, eGRID2022 average, 823.1 lb/MWh); world 0.471 (Ember, 2024).
    • Natural gas: 0.183 kg CO₂e/kWh on a gross calorific basis (DESNZ conversion factors), close to the US EPA figure of 5.3 kg CO₂ per therm (0.181 kg/kWh).
    • All energy figures are annual kWh. Factors are averages, not marginal rates, and exclude upstream (well-to-tank) emissions.

    Worked example (the default inputs)

    A building uses 1,000,000 kWh of electricity (25% lighting, 40% HVAC, 35% other) and 800,000 kWh of gas. Lighting: 250,000 × 0.625 = 156,250 kWh saved. HVAC (scheduling, fault detection, drives): 1 − 0.90 × 0.92 × 0.85 = 29.62%, so 118,480 kWh. Gas (scheduling, fault detection, envelope): 1 − 0.90 × 0.92 × 0.80 = 33.76%, so 270,080 kWh. Total 544,810 kWh, 30.3% of baseline. At €0.20 and €0.07 per kWh the saving is €73,852 a year, a 3.4-year payback on €250,000, and 107.9 t CO₂e a year on the EU factors. Tick the heat pump (SCOP 3.0, boiler 90%) and the 529,920 kWh of remaining gas becomes 158,976 kWh of electricity: €79,151 and 171.1 t CO₂e a year.

    Limitations

    Interactions between measures are only approximated, and lighting retrofits can raise heating demand slightly. Weather, occupancy and tariff changes are ignored. For investment-grade figures, measure savings against an adjusted baseline using IPMVP or ASHRAE Guideline 14, as described in our guide to measurement and verification of energy savings. Related reading: fault detection in building systems, intelligent building management systems and heat pumps explained.