Monitoring Energy Consumption: From Monthly Bills to Interval Data
How to turn utility bills, smart-meter interval data and sub-meters into useful insight: base load, weather normalisation, CUSUM and a monitoring routine.

Most organisations already own a surprising amount of energy data. There is a pile of monthly invoices, probably a smart or half-hourly meter on the main electricity supply, perhaps a gas data logger, and almost certainly a building management system quietly storing trends that nobody opens. What is usually missing is not data but a habit of looking at it in a way that reveals waste.
This article works through the ladder of data resolution, from monthly bills to 15-minute interval data and sub-meters, and shows what each rung can and cannot tell you. Along the way it covers three techniques that repay the effort many times over: reading a daily load profile, normalising consumption for weather, and using cumulative sum (CUSUM) charts to catch drift before it shows up in the annual accounts.
What each level of data can tell you
Resolution is the first thing to understand, because it sets the questions you can ask. A monthly total can tell you whether the building used more gas this January than last; it cannot tell you that the boilers fire at 03:00 every Sunday.
| Data source | Typical resolution | Good for | Blind to |
|---|---|---|---|
| Utility invoices | Monthly or quarterly, sometimes estimated | Annual totals, cost trends, weather regression | Time-of-day waste, short faults |
| Manual meter reads | Weekly or monthly | Verifying invoices, simple trends | Anything within the reading interval |
| Smart / interval meters | 15 or 30 minutes | Load profiles, base load, out-of-hours use, peak demand | Which system is responsible |
| Sub-meters | 1–30 minutes | Attribution to plant, tenants or processes | Unmetered loads |
| BMS trend logs | Seconds to minutes | Diagnosing control behaviour | Energy (unless metered points are trended) |
The practical lesson is that each level answers a different question, so you rarely need to choose. Bills establish the annual picture and financial context; interval data finds behavioural and control waste; sub-meters attribute it. Our guide to designing a sub-metering strategy covers the third step in detail.
Start with the bills
Before buying anything, load two or three years of monthly invoices into a spreadsheet. Check for estimated reads (they often appear as suspiciously smooth months followed by a large correction), tariff changes and billing periods that do not align with calendar months. Convert everything to kWh; gas is often billed in volume and converted using a calorific value printed on the invoice.
Then plot monthly heating fuel against heating degree days (HDD) for the same periods. Degree days measure how far, and for how long, outdoor temperature fell below a base temperature, and they are published for most locations. If the building is weather-driven, the points fall roughly on a straight line:
E = a + b × HDD
where E is monthly consumption (kWh), a is the weather-independent component (hot water, catering, process loads, standing losses) and b is the consumption per degree day. A tight fit (many practitioners look for an R² of roughly 0.75 or better in a heating-dominated building) tells you the model is usable. A poor fit is information too: it suggests heating that is not responding to weather, perhaps because of manual overrides or a fixed schedule.
Consider an illustrative office whose regression gives a = 12,000 kWh per month and b = 95 kWh per degree day. In a month with 350 HDD the expected gas use is 12,000 + 95 × 350 = 45,250 kWh. The intercept alone is revealing: 12,000 kWh every month, even in summer, is worth questioning if the building has no catering.
Reading an interval profile
Interval data, usually at 30-minute resolution in the UK and Ireland and 15-minute in much of continental Europe and North America, is where most quick wins are found. Plot a typical week as a line chart, or better, as a heat map with days down the side and time across the top. Then look for five features.
- Base load. The lowest sustained demand, normally overnight. It represents everything that never switches off: servers, refrigeration, emergency lighting, standby losses, and anything left running by mistake.
- Night-to-day ratio. In a conventional office, overnight demand that is a large fraction of the daytime peak suggests a lot of equipment is not following occupancy. Compare the ratio across similar buildings you manage.
- Start-up and shut-down times. Does demand rise at 05:00 for an 08:30 opening? Optimum start should bring plant on only as early as needed for the weather.
- Weekends and holidays. A Saturday profile that looks like a weekday is one of the most common findings in any building portfolio.
- Peaks. Short spikes may drive capacity or demand charges. Check whether they coincide with simultaneous plant starts that could be staggered.
Worked example: what a base load costs
Consider an office occupied 08:00–18:00 on weekdays. Out-of-hours time is 8,760 − (10 h × 5 days × 52 weeks) = 6,160 hours per year. If the overnight base load is 40 kW and an investigation shows that 15 kW of it is avoidable (ventilation fans on a faulty schedule, lighting circuits left on, idle IT), the annual saving is:
15 kW × 6,160 h = 92,400 kWh per year
At an assumed €0.20 per kWh that is €18,480 a year, typically achieved with schedule changes rather than capital spending. The electricity cost calculator is handy for running the same arithmetic with your own tariff.
Normalising for weather and activity
Raw month-on-month comparisons mislead because weather, occupancy and production vary. Normalisation removes the variation you cannot control so that the variation you can control becomes visible.
For heating, divide by degree days or, better, use the regression above to calculate expected consumption for the actual weather. For cooling, use cooling degree days in the same way. For buildings with significant variation in activity, add a second variable such as occupied hours, bed-nights or production tonnage. Multivariable regression works, but keep the model as simple as the data supports; two or three well-chosen drivers usually beat ten weak ones.
Normalised figures are the foundation of energy performance indicators. If you are building a formal energy management system, our article on energy performance indicators and baselines explains how to select and maintain them.
CUSUM: catching drift early
A CUSUM chart plots the running total of the difference between actual and expected consumption. When performance matches the model, the line wanders around zero. When something changes, the slope changes, and the point where it bends tells you when.
Continuing the illustrative office, with expected gas use from E = 12,000 + 95 × HDD:
| Month | HDD | Expected (kWh) | Actual (kWh) | Difference (kWh) | CUSUM (kWh) |
|---|---|---|---|---|---|
| Jan | 350 | 45,250 | 45,900 | +650 | +650 |
| Feb | 300 | 40,500 | 40,100 | −400 | +250 |
| Mar | 230 | 33,850 | 34,200 | +350 | +600 |
| Apr | 130 | 24,350 | 26,900 | +2,550 | +3,150 |
| May | 60 | 17,700 | 20,300 | +2,600 | +5,750 |
| Jun | 20 | 13,900 | 16,400 | +2,500 | +8,250 |
From January to March the differences are small and change sign, which is normal scatter. From April the CUSUM climbs steadily by about 2,500 kWh a month. Something changed at the end of March: perhaps the heating time clock was reset after the clock change, a valve stuck open, or a summer setback was never applied. The chart does not diagnose the cause, but it narrows the search to a specific date and a specific magnitude, which is most of the battle.
The same logic underpins formal savings verification. When you later implement an efficiency measure, a downward bend in the CUSUM is your first evidence that it is working, and a rigorous version of that comparison is the subject of measurement and verification of energy savings.
Data quality: the unglamorous part
Monitoring fails more often because of bad data than bad analysis. Common problems include:
- Gaps and zeros. Communication outages often appear as zero consumption followed by a spike. Flag them rather than averaging over them.
- Wrong multipliers. Current-transformer ratios and pulse weights set incorrectly at commissioning can make a meter read 10 or 100 times too high or low. Always reconcile sub-meters against the main meter.
- Clock and daylight-saving issues. Interval timestamps may be in local time, UTC, or period-ending versus period-starting. Misalignment creates phantom shifts in profiles.
- Unit confusion. kW versus kWh per interval is a classic error: a 30-minute reading of 20 kWh corresponds to an average demand of 40 kW.
- Meter replacements. A new meter may reset cumulative registers. Record replacement dates.
A simple check is to sum interval data for a month and compare it with the invoice for the same period. Agreement within a percent or two gives confidence in both.
A monitoring routine that sticks
Analysis that happens once is an audit; analysis that happens every week is monitoring. The organisations that sustain savings tend to have a light, regular routine with clear ownership. A workable pattern:
- Weekly (15 minutes): review the previous week's interval profile for each main meter against a reference week. Look at overnight and weekend demand first.
- Monthly (1 hour): update degree-day regressions and CUSUM charts; reconcile meters with invoices; log any anomalies and actions.
- Quarterly: review energy performance indicators with facilities and finance; confirm that previous fixes have held.
- Annually: re-fit baseline models, retire obsolete ones, and check whether the metering still matches how the building is used.
Two practical points make this easier. First, automate the tedious parts: most energy software can flag base-load creep or weekend use automatically, and well-designed dashboards that people actually use keep attention on the few indicators that matter. Second, record every finding and action in a simple log, even when the cause is unknown. Over time that log becomes the institutional memory that stops the same fault being rediscovered every winter.
Key takeaways
- Use each data resolution for what it does best: bills for annual context, interval data for time-of-day waste, sub-meters for attribution.
- Base load and out-of-hours demand are the first places to look, and fixing them is often free.
- Normalise for weather and activity before comparing periods; a degree-day regression is a five-minute job in a spreadsheet.
- CUSUM charts show when performance changed and by how much, which turns a vague concern into a focused investigation.
- Check data quality relentlessly, and build a short, regular review habit with a named owner.